APC Smart-UPS C 1000VA LCD 120V - 2U Rackmount
APC Smart-UPS, 600 Watts / 1000 VA, Input 120V / Output 120V , Interface Port USB , Rack Height 2U

APC Smart-UPS C 1000VA LCD 120V - 2U Rackmount

Includes: CD with software, Documentation CD, Installation guide, Rack Mounting brackets, USB cable

Sorry, this product is no longer available, Please contact us for a replacement.

 

Brings Smart-UPS reliability to entry-level applications.

APC Smart-UPS C is ideal for small and medium businesses looking to protect entry-level servers and networking equipment from power disturbances and outages. APC Smart-UPS C features pure sine wave output on battery, simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics. LCD status display provides key UPS status at a glance. Multiple status indicators with load and battery bar graphs. Most Smart-UPS C models can be installed in either a tower or rack configuration, allowing standardization across multiple applications. Built on the same standards as the award-winning Smart-UPS, with over 10 million installed, Smart-UPS C provides the basic features and manageability needed to protect entry-level applications.

SMC1000-2U Rear

Features & Benefits:

SMC1000-2U Features
Green mode Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
Pure sine wave output on battery Simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.
LCD Status Display Provides key UPS status at a glance. Multiple status indicators with load and battery bar graphs.
High online efficiency Reduces utlility costs, generates less heat.
Cold-start capable Provides temporary battery power when the utility power is out.
Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
Availability
Boost and Trim Automatic Voltage Regulation (AVR) Gives higher application availability by correcting low and high voltage conditions without using the battery (not available on all models).
Intelligent battery management Maximizes battery performance, life, and reliability through intelligent, precision charging.
Power conditioning Protects connected loads from surges, spikes, lightning, and other power disturbances.
Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
Automatic restart of loads after UPS shutdown Automatically starts up the connected equipment upon the return of utility power.
Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Disconnected battery notification Warns when a battery is not available to provide backup power.
Manageability
Network manageable Provides remote management of the UPS over the network.
Audible alarms Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition.
LED status indicators Quickly understand unit and power status with visual indicators.
Serial Connectivity Provides management of the UPS via a serial port.
USB connectivity Provides management of the UPS via a USB port (not available on all models).
Disconnected battery notification Warns when a battery is not available to provide backup power.
Serviceability
User-replaceable batteries Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Predictive failure notification Provides early-warning fault analysis ensuring proactive component replacement.
Resettable circuit breakers Enables a quick recovery from overload events.
Battery failure notification Provides early-warning fault analysis on batteries enabling timely preventive maintenance
Adaptability
Adjustable voltage-transfer points Maximizes useful battery life by widening the input voltage window or tightening the output voltage regulation.
Adjustable voltage sensitivity Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.
Safety
Safety-agency approved Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.

Technical Specifications:

Output
Output Power Capacity 600 Watts / 1000 VA
Max Configurable Power 600 Watts / 1000 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 50/60Hz +/- 3 Hz
Topology Line Interactive
Waveform Type Sine wave
Output Connections NEMA 5-15R(6) NEMA 5-15R
Input
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections NEMA 5-15PNEMA 5-15P
Cord Length 8 feet (2.44 meters)
Input voltage range for main operations 93 - 130V
Input voltage adjustable range for mains operation 85 - 136V
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leakproof
Typical recharge time 3 hour(s)
Replacement Battery APCRBC124
RBC™ Quantity 1
Runtime Graph Runtime Graph Chart
Hover over the line on the graph above to view the runtime at any desired load

Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Energy Use/Efficiency
Load Efficiency
25% 93.5%
50% 96.3%
75% 97.1%
100% 97.4%
Energy Use/Efficiency Chart
Hover over the line on the graph above to view the efficiency at any desired load

Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Communications & Management
Interface Port(s) USB
Control panel Multi-function LCD status and control console
Audible Alarm Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO) --
Surge Protection and Filtering
Surge energy rating 455 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height 3.50 inches (89 mm)
Maximum Width 17.00 inches (432 mm)
Maximum Depth 16.00 inches (406 mm)
Rack Height 2U
Net Weight 45.15 lbs. (20.52 kg)
Shipping Weight 49.12 lbs. (22.33 kg)
Shipping Height 9.50 inches (241 mm)
Shipping Width 21.50 inches (546 mm)
Shipping Depth 23.00 inches (584 mm)
Color Black
Units per Pallet 16.00
Environmental
Operating Environment 32 - 104°F (0 - 40°C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature 5 - 113 °F (-15 - 45 °C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit 42.00 dBA
Online Thermal Dissipation 81.00 BTU/hr
Conformance
Regulatory Approvals CSA,NOM,UL 1778
Standard Warranty 2 years repair or replace
Equipment protection policy Lifetime: $150000
Environmental Compliance RoHS 7b Exemption,REACH: Contains No SVHCs

Documentation:

Download the APC SmartUPS C SMC1000/1500 Data Sheet (PDF).

It appears you don't have a PDF plugin for this browser. No biggie... you can click here to download the PDF file.